Compares indoor and outdoor air by total heat content (temperature and moisture), then prices the difference with your own equipment.
| Inside | Outside | Outside − inside |
|---|
Method: saturation vapor pressure from the Buck (1981) equation; humidity ratio W = 0.62198·Pw/(P−Pw); moist-air enthalpy h = 1.006·T + W·(2501 + 1.86·T) kJ/kg; latent heat ≈ 2465 kJ/kg. In AC mode, the total load through the coil is m·Δh and electricity is load ÷ COP. In dehumidifier mode, imported moisture costs (liters ÷ IEF) kWh, and all of that electricity plus the latent heat of the condensed water is released into the room as heat. Everything here is a steady-state estimate that ignores thermal mass, fan energy, and infiltration you'd have anyway.